Típico Fator de Potência
Average Power Factor values for the most commonly used plant, equipment and appearances: plant and appliances cos φ tan φ induction motor - loaded at 0% 0.17 2.80 induction motor - loaded at 25% 0.55 1.52 induction motor - loaded at 50% 0.73 0.94 induction motor - loaded at 75% 0.80 0.75 induction motor - loaded at 100% 0.85 0.62 lamps incandescent 1.0 0 lamps fluorescent (uncompensated) 0.5 1.73 lamps fluorescent (compensated) 0.93 0.39 lamps discharge 0.4 to 0.6 2.29 to 1.33 oven resistance elements 1.0 0 oven induction heating (compensated) 0.85 0.62 oven dielectric heating 0.85 0.62 resistance type soldering machines 0.8 to 0.9 0.75 to 0.48 arc-welding fixed 1-phase 0.5 1.73 arc-welding motor-generator set 0.7 to 0.9 1.02 to 0.48 arc-welding transformer-rectifier set 0.7 to 0.8 1.02 to 0.75 arc furnace 0.8 0.75 Source: Groupe Schneider - Electrical installation guide (According to IEC International Standards), 1996 - See more at: http://myelectrical...